Transformer Turns Ratio Tester
ATRT-01 S3, ATRT-01B S3


  • Standalone or computer-controlled
  • Inexpensive
  • Displays turns-ratio from 0.8-15,000
  • Calculates turns-ratio percentage error
  • Displays winding polarity and phase angle
  • Displays excitation current


    TYPETransformer Turns Ratio Tester
    PHYSICAL SPECIFICATIONS Dimensions: 12” x 10” x 8” (30.4 cm x 25.4 cm x 20.3 cm)
    Weight: 8 lbs. (3.6 Kg)
    INPUT POWER120 or 240 Vac (Selectable), 50/60 Hz
    MEASURING METHOD ANSI/IEEE C57.12.90
    RATIO MEASURING RANGE 0.8 - 15,000 (5 digit resolution)
    TURNS-RATIO ACCURACY 40 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (1%)
    4 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (2%)
    TEST VOLTAGE 4 Vac @ 1.0A, 40 Vac @ 0.6A
    PHASE ANGLE MEASUREMENT 0 - 360 degrees, Accuracy ±0.2 degree (±1 digit)
    POLARITY READINGIn-Phase or Out-of-Phase indication
    EXCITATION CURRENT READING RANGE0-2 Amperes, Accuracy: 2% of reading (±1 mA)
    DISPLAYBack-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels
    COMPUTER INTERFACERS-232C
    PC SOFTWARE Windows XP/Vista/7 Transformer Analysis Software (included with purchase)
    INTERNAL TEST RECORD STORAGE128 records of 33 readings
    EXTERNAL TEST RECORD STORAGEUp to 999 test records on external USB Flash drive.
    SAFETYDesigned to meet IEC 61010 (1995), UL 61010A-1, and CSA-C22.2 standards
    ENVIRONMENTOperating: -10ºC to 50ºC (15ºF to +122ºF)
    Storage: (-30ºC to 70ºC (-22ºF to +158ºF)
    HUMIDITY (MAX)90% RH @ 40˚ C (104˚ F) non-condensing
    ALTITUDE (MAX)2000m (6562 ft) to full safety specifications
    CABLESOne 15 ft. (4.6m) Single phase cable, one power cord, one cable bag
    OPTIONSTransportation Case (Can hold unit and cables)
    WARRANTYOne year on parts and labor